Customization: | Available |
---|---|
Task: | Program |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General | |
Number of channels | 1input/1output |
Output accuracy (20 ° C) | 0.2% F.S. |
Temperature drift | 50ppm/K |
Response time | <0.5s (0~90%) (TYP) |
Insulation strength | 1500V AC/1min,2mA |
Insulation resistance | Above 100M Ω at 500VDC |
Electromagnetic compatibility | Compliant with GB/T18268 (IEC61326-1) |
Weight | About 120g |
Connected field equipment | Two wire thermistor, three wire thermistor |
Input data | |
Input signal | PT100;PT100;CU50 |
Output data | |
Output signal | PT100;PT100;CU50 |
Power supply | |
Supply voltage(Ue) | 24VDC±25% |
Power protection | Reverse protection of power supply |
Power consumption | <1W |
Power supply mode | Independent power supply |
Power connecting mode | Terminal power supply |
Overall dimension | |
Depth | 110mm |
Height | 108mm |
Width | 13.3mm |
Housing | |
Material | PC+ABSflame retardant |
Degree of protection | IP20 |
Flammability rating | UL94/V0 |
Colour | Grey |
EMC data | |
Electrical fast transient/burst immunity | Compliant with:IEC 61326-1;A-leve |
Surge immunity | Compliant with:IEC 61326-1;B-leve |
Radiated,radio-frequency,electromagnetic field immunity | Compliant with:IEC 61326-1;conform to basic requirements |
Electrostatic discharge immunity | Compliant with:IEC 61326-1;A-leve |
Immunity to conducted disturbances, induced by radio-frequency fields | Compliant with:IEC 61326-1;conform to basic requirements |
Low frequency common mode conduction | Compliant with:IEC 61326-1;conform to basic requirements |
Operating conditions | |
Continuous operating temperature | -20ºC~+60ºC |
Storage temperature | -40ºC~+80ºC |
Relative humidity | < 90% RH(no condensate) |
Environmental requirements | There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances |
Connection data | |
Conductor cross section solid range | 0.5~2.5mm² |
Conductor cross section AWG min. | 12 |
Conductor cross section AWG max. | 24 |
Stripping length | 8mm |
Screw thread | M3 |
Connection method | Screw connection |
Tightening torque min. | 0.5 Nm |
Tightening torque max. | 0.6 Nm |
Installation | |
Installation method | DIN35mm |
1.Q: Who are we?
A: We are a high-tech enterprise dedicated to the research and development, production, and sales of industrial automation signal acquisition, processing, and communication products. Headquartered in Nanjing, China, our company offers comprehensive pre-sales, after-sales, and technical services globally. Our primary products include remote I/O modules, safety barriers, isolators, safety relays, surge protectors, power transmitters, industrial switches, serial servers among others.
2.Q: Why should you choose us over other suppliers?
A: Our company is committed to ensuring equipment interface safety at industrial sites. Our products are utilized worldwide across various sectors including electric power generation; petroleum and petrochemical industries; steel manufacturing; cement production; environmental protection; metallurgy; mining operations; aerospace applications; textiles manufacturing; pharmaceuticals distribution; transportation logistics; shipbuilding activities as well as plastics and rubber production processes.
3.Q: How do you ensure quality?
A: Paragon Technology consistently adheres to the business philosophy of "conducting world-class standards." We strive to provide our customers with high-quality products alongside exceptional service and comprehensive technical support.
4.Q: Do you accept OEM or ODM orders?
A: Yes. Please share your specific requirements with us.
5.Q: What is your minimum order quantity (MOQ)?
A: The minimum order quantity is one unit.
6.Q: What is the warranty period for your product?
A: The warranty period is one year (covering non-human-induced damages).