Customization: | Available |
---|---|
Certification: | RoHS, CCC, ISO: 9001, CE |
Condition: | New |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General | |
Number of channels | 1input/1output |
Output accuracy (20 ° C) | 0.2% F.S. (typical value: 0.05% F.S.) |
Temperature drift | <30ppm/ºC |
Response time | <2ms |
Insulation strength | 1500VAC/min between intrinsically safe/non intrinsically safe terminals, 1000VAC/min between non intrinsically safe terminals |
Insulation resistance | Non intrinsic safety end - intrinsic safety end≥100MΩ, power supply - non intrinsic safety end≥100MΩ |
Electromagnetic compatibility | EMC compliant with IEC 61241-1-2004 |
Weight | About 130g |
Connected field equipment | Sensor load |
Applicable locations | Zone 0, Zone 1, Zone 2, IIA, IIB, IIC,T4-T6 hazardous areas |
Recommended operating voltage | 12V |
Maximum withstand voltage | 13V |
Terminal resistance | 25Ω |
Grounding resistance | <1Ω |
Input and output data | |
Input voltage (safety side) | Load current Output voltage |
12V | 40mA 11V |
12V | 80mA 10V |
12V | 120mA 9V |
12V | 160mA 8V |
12V | 240mA 6V |
12V | 280mA 5V |
12V | 360mA 3V |
12V | 480mA 0V |
Recommended associated device parameters: Working voltage range: 5-12V, power consumption ≤ 1.5W | |
Power application | |
1. Analog signal | |
2. Switching signal | |
3. 12V frequency pulse signal | |
4. Communication signals | |
Power supply | |
Power supply mode | Independent power supply |
Power connecting mode | Terminal power supply |
Overall dimension | |
Depth | 110mm |
Height | 99mm |
Width | 12.5mm |
Housing | |
Material | ABSflame retardant |
Degree of protection | IP20 |
Flammability rating | UL94/V0 |
Colour | Black |
EMC data | |
Electrical fast transient/burst immunity | Compliant with:IEC 61326-1;A-leve |
Surge immunity | Compliant with:IEC 61326-1;B-leve |
Radiated,radio-frequency,electromagnetic field immunity | Compliant with:IEC 61326-1;conform to basic requirements |
Electrostatic discharge immunity | Compliant with:IEC 61326-1;A-leve |
Immunity to conducted disturbances, induced by radio-frequency fields | Compliant with:IEC 61326-1;conform to basic requirements |
Low frequency common mode conduction | Compliant with:IEC 61326-1;conform to basic requirements |
Operating conditions | |
Continuous operating temperature | -20ºC~+60ºC |
Storage temperature | -40ºC~+80ºC |
Relative humidity | 5%~95%RH(40ºC) |
Environmental requirements | There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances |
Connection data | |
Conductor cross section solid range | 0.5~2.5mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Stripping length | 8mm |
Connection method | Screw connection |
Tightening torque min. | 0.5 Nm |
Tightening torque max. | 0.6 Nm |
Installation | |
Installation method | DIN35mm |