Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General | |
Number of channels | 1input/1output |
Output accuracy (20 ° C) | 0.1% F.S. (typical value: 0.05% F.S.) |
Temperature drift | 0.005%F.S./ºC |
Response time | 2ms to reach 90% of the final value |
Insulation strength | 1500VAC/min between intrinsically safe/non intrinsically safe terminals, 1000VAC/min between non intrinsically safe terminals |
Insulation resistance | Non intrinsic safety end - intrinsic safety end≥100MΩ, power supply - non intrinsic safety end≥100MΩ |
Electromagnetic compatibility | Compliant with IEC 61326-1(GB/T 18268),IEC 61326-3-1 |
EX marking | [Ex ia Ga]IC |
Weight | About 150g |
Connected field equipment | Two wire transmitter (HART); Three wire transmitter; Current source signal |
Applicable locations | Zone 0, Zone 1, Zone 2, IIA, IIB, IIC hazardous areas |
Input data | |
Input signal | 4mA~20mA/1~5V |
Output data | |
Output signal | 4mA~20mA/1~5V |
Distribution output power supply | When the output current is 20mA, the distribution voltage is greater than 16V |
Power supply | |
Supply voltage(Ue) | 20~35V DC |
Power protection | Reverse protection of power supply |
Power consumption | 1.5W (24V power supply, 20mA output) |
Power supply mode | Independent power supply |
Power connecting mode | Terminal power supply;Base power supply |
Overall dimension | |
Centralized power supply | |
Depth | 120.8mm |
Height | 113mm |
Width | 13.3mm |
Independent power supply | |
Depth | 110mm |
Height | 108mm |
Width | 13.3mm |
Housing | |
Material | PC+ABSflame retardant |
Degree of protection | IP20 |
Flammability rating | UL94/V0 |
Colour | White+Grey |
EMC data | |
Electrical fast transient/burst immunity | Compliant with:IEC 61326-1;A-leve |
Surge immunity | Compliant with:IEC 61326-1;B-leve |
Radiated,radio-frequency,electromagnetic field immunity | Compliant with:IEC 61326-1;conform to basic requirements |
Electrostatic discharge immunity | Compliant with:IEC 61326-1;A-leve |
Immunity to conducted disturbances, induced by radio-frequency fields | Compliant with:IEC 61326-1;conform to basic requirements |
Low frequency common mode conduction | Compliant with:IEC 61326-1;conform to basic requirements |
Operating conditions | |
Continuous operating temperature | -20ºC~+60ºC |
Storage temperature | -40ºC~+80ºC |
Relative humidity | 10%~90% |
Environmental requirements | There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances |
Connection data | |
Conductor cross section solid range | 0.5~2.5mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 8mm |
Screw thread | M3 |
Connection method | Screw connection |
Tightening torque min. | 0.5 Nm |
Tightening torque max. | 0.6 Nm |
Installation | |
Installation method | DIN35mm |
Attention | |
Usage restrictions | 1. HHC (HART manual operator) cannot be used simultaneously in hazardous and safe areas 2. HHC (HART manual operator) used in hazardous areas must have explosion-proof certification |