Customization: | Available |
---|---|
Certification: | RoHS, CCC, ISO: 9001, CE |
Condition: | New |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General | |
Output accuracy (20 ° C) | ± 0.5% |
Response time | <400ms |
Insulation strength | 1500V AC/1min,2mA |
Insulation resistance | Above 100M Ω at 500VDC |
Electromagnetic compatibility | Compliant with GB/T18268 (IEC61326-1) |
Weight | About 200g |
Connected field equipment | Current source |
Overload capacity | Can withstand 2 times the rated value (continuous), 10 times the rated value (10s) |
Power consumption | About 4VA |
Input data | |
Input signal | 1A;5A;100V,220V,380V |
Input load | Voltage transformer PT: ≤ 0.1VA |
Current transformer CT: ≤ 0.2VA | |
Output data | |
Output signal | Output current: 0~20mAdc,4~20mAdc |
(Load resistance=10Vdc/output current0; Output voltage: 0 ~ 10Vdc,0 ~ 5Vdc |
|
(Load resistance=input voltage/10mAdc) | |
Output ripple | ≤0.5%RO |
Overall dimension | |
Length | 109mm |
Height | 119mm |
Width | 75mm |
Housing | |
Material | ABS flame retardant |
Degree of protection | IP20 |
Flammability rating | UL94/V0 |
Colour | Black |
EMC data | |
Electrical fast transient/burst immunity | Compliant with:IEC 61326-1;A-leve |
Surge (impact) immunity | Compliant with:IEC 61326-1;B-leve |
Radiated,radio-frequency,electromagnetic field immunity | Compliant with:IEC 61326-1;conform to basic requirements |
Electrostatic discharge immunity | Compliant with:IEC 61326-1;A-leve |
Immunity to conducted disturbances, induced by radio-frequency fields | Compliant with:IEC 61326-1;conform to basic requirements |
Low frequency common mode conduction | Compliant with:IEC 61326-1;conform to basic requirements |
Operating conditions | |
Operating temperature | 0~50 ºC/less than 80% relative humidity (non condensing state) |
Storage temperature | -20ºC~+70ºC/less than 70% relative humidity (non condensing state) |
Relative humidity | < 90% RH(no condensate) |
Environmental requirements | There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances |
Connection data | |
Conductor cross section solid range | 0.5~2.5mm² |
Conductor cross section AWG min | 12 |
Conductor cross section AWG max | 24 |
Stripping length | 8mm |
Screw thread | M3 |
Connection method | Screw connection |
Tightening torque min. | 0.5 Nm |
Tightening torque max. | 0.6 Nm |
Installation | |
Installation method | DIN35mm |